Setting up the Digi One IA RealPort as a Modbus Serial Slave with Kepware Setting up the Digi One IA RealPort as a Modbus Serial Slave with Kepware
NOTE: This example was setup using
a Schneider Compact 265 running Kepware KepServerEX 4.71.201 -U and Kepware OPC
Quick Client 4.30.74 -U. Therefore the application section may not apply to you, but may
offer some insight on configuring your application to talk to the Digi One
RealPort (IA).
NOTE: You will want to install Digi Port Authority Remote to give
the IP Address to the Digi One Device.
If you do not already have it, you can download it from www.digi.com.
The installation instructions can be found in the setup
guide.
1. After installing Digi Port Authority Remote, you can run it by
going to Start, Programs, Digi, Digi Port Authority - Remote and select
Digi Port Authority - Remote (see Figure
1).

2. Click on Discover to find
your Digi One RealPort (IA). If you are on a DHCP network, you will automatically
obtain an IP Address.
If not, you can assign an IP Address by clicking on Configure
to assign and IP.

3. Once an IP Address is assigned, click on Configure
to launch the web browser and finish the Digi One RealPort (IA) configuration.
4. Log into the Digi One RealPort (IA) by entering the
default username: root and password: dbps.

5. Once the browser is launched (notice your Digi One RealPort
(IA) IP
Address in the address field of your internet browser),
you can finish
the Digi One RealPort (IA) configuration. After
logging in select Configure, Port.

6. In the Device Type drop down box, change the
device type for port 1 to IA.

7. Select the appropriate baud rate, data bits, parity, stop bits and
flow control to match the requirements of your PLC.
8. Click on the Advanced button
at the bottom of the page.
9. Click on the box next to Force
DCD to enable it.

10. Click Submit
at the bottom of the page to save changes.
11. In the Browser window use the Back button to go back to the Port
Configuration Page.
12. Click Industrial
Protocols at the bottom of the page
to save changes.
12. If your PLC uses ASCII encoding rather than RTU,
select Modbus ASCII from the Protocol drop
down box .
NOTE: If your PLC uses
RTU encoding, do not change this setting!

13. Click Submit
to save changes.
14. Your Digi One RealPort (IA) is successfully
configured and you can either click on the back button in your web browser to go
back to
the main Port Configuration screen
or close your web browser.
15. You will now need to configure your application.
THIS IS AN EXAMPLE ONLY (using Schneider Compact 265 running
Kepware KepServerEX 4.71.201 -U and Kepware OPC Quick Client 4.30.74 -U):
If this doesn't apply to you, this section maybe skipped and you can configure
the application you are using to communicate to the Digi One
RealPort (IA). This is meant as an example of how an application may be
configured to successfully communicate to the Digi One RealPort (IA).
16. Next launch your Kepware KepServer EX software and
click on the option to add a channel.

17. In the Channel name box, assign a name to the new
channel. Click Next

18 . In the device driver drop down box, select Modbus
Serial to configure a Modbus Serial Slave PLC. Click Next.

19. Click on the box labeled Use
Ethernet Encapsulation. Click Next.

20. After completing the channel information, you will
get a summary screen of configuration. If everything is correct, click
Finish.

21. You will now need to add a device to the channel you
just created. To do so, click on the option to add a device.
22. In the Device name box, assign a name to the new
device. Click Next
23. Next, you will be prompted for the type of device
you are configuring. In this case we are setting up a Modbus Serial Slave
PLC so will
choose Modbus from the Device Model drop
down box. Click Next.

24. You will now be prompted to assign a unique ID to
your device. Using the Device ID drop down box, you can specify a new
Device
ID.
The
device ID is the address of the Modbus slave. Click Next.

25. Click on the Ethernet Encapsulation tab. You
will need to enter the IP Address of the Digi One RealPort (IA) in the IP
Address
box and set the Port Number to 2101.
The TCP Socket the Digi One RealPort (IA) talks at is 2000. To send raw
data on port
1, you would need to set the Port Number to
2101.

26. After completing the device information, you will
get a summary screen of configuration. If everything is correct, click
Finish.

27. If you want to add a static for OPC clients to browse, click on the
option to add a static tag.

28. Create a name.
NOTE: This is just a label, so
anything works here.
Next, enter the Address (register) you wish
to communicate with in the PLC.
NOTE: 40001 is a status address
common to most Modbus systems.
Click on the Green Check Mark to verify
whether the Address you have entered is valid.
Add a Description, if you desire (not
required) and accept all other defaults.

29. You will now see the new tag in the right hand window pane for your
device.

30. Now highlight the Tag you created, then click
on the OPC Quick Client Icon (Hammer Icon) to test the communications.
Click on Channel1.Device1 to expose the OPC
Tag on the right hand side of your screen.
By looking at the value in the Quality
column you will be able to determine if the communications are successful.
If the value is "Good", you are
talking.
|