|
Frequently
Asked Questions
Windows NT and the
T1 Modem Bank |
-
What are the most current driver files for the T1
Modem Bank for Windows NT?
- Select File Manager (NT 3.51) or Windows Explorer (NT
4.0). In the following path:
<WINNT>/System32/Drivers, select the DIGIFEP5.*
file. Highlight this file and click on "File",
"Properties". A description will be displayed
which includes the version number.
- What driver
should I install for my intelligent asynchronous Digi
product?
The drivers that ship with Microsoft Windows NT 3.51,
and NT 4.0 are no longer the most current Digi drivers
for NT. The current released driver is version 2.1.0, and
may be downloaded either from the BBS or the ftp site.
The downloadable filename is 4000821R.exe for Windows NT
3.51 and NT 4.0. [4001438K.exe for Windows NT 3.50]
You will also need to download installr.txt, which
contains installation instructions for both Windows NT
3.51 and Windows NT 4.0.
- The event viewer error message: "Wait
confirmation failed" means?
- Check the dip switch settings on the board. Typically
this error message indicates that the dip switch settings
on the board do not match the I/O address chosen in the
driver configuration.
Verify that the correct driver
has been installed for the Digi product. An incorrect
driver will also cause this error message.
Verify that the I/O address chosen does not conflict
with any other devices in the system.
- The event viewer error message: "BIOS
image failed to load" means?
- Verify that the memory address chosen does not conflict
with any other devices in the system.
If the system is
an ISA machine, verify that shadowing has been disabled
in the CMOS setup for the memory range the Digi board is
being installed in.
If the system is an EISA machine, verify that the
board has been configured in the system's EISA
configuration utility, and that the settings chosen in
the ECU match the settings chosen when the driver was
configured.
If the system is a MCA machine, verify that the board
has been configured with the reference diskette for the
system, and that the settings chosen match the settings
chosen when the driver was configured.
If there are no known memory conflicts, and shadowing
has been disabled, run the DOS diagnostic for the Digi
product to verify the hardware.
- The following event viewer error message : "While
validating that COMx was really a serial port, the
contents of the divisor
latch register was identical to the interrupt enable and
the receive registers. The device is assumed not to be a
serial port and will be deleted" means?
Most likely conflicting non-intelligent port(s) have
been configured. This usually occurs when changes are
made in Control Panel, Ports. The conflict must be
removed either by changing the names of the Digi ports to
avoid the conflict or by removing the conflicting serial
port configuration(s).
- To remove these error messages, follow these steps:
- Start the registry editor by typing "start
regedt32" from the command prompt.
- Select the following: HKEY_LOCAL_ MACHINE on Local
Machine, System, CurrentControlSet, Services, Serial,
Parameters. Typically, no keys should be listed beneath
Parameters. Check the values of any keys listed to locate
the conflicting serial port(s).
- Delete any conflicting keys under Parameters. Highlight
the serial port key and press "Delete". Repeat
for each conflicting serial port configuration. Reboot
the system and check the event viewer to verify that the
error messages do not reoccur. The errors may reappear
later if any operations are attempted in Control Panel,
Ports.
- CAUTION: Any mistakes made in editing the registry may
have disasterous results requiring you to boot to a
different Control Set or to reload Windows NT.
- The following event viewer error message(s) : "User
configuration for parameter ntx*Line1Concentrator1Port1
must have PortAddress." "User
configuration for parameter Serial0 must have
PortAddress." means?
These errors are a result of a bug in the Control
Panel, Ports applet. The problem has been reported to
Microsoft. To remove these error messages, follow these
steps:
- Start the Registry Editor by typing "start
regedt32" at a command prompt.
- Select the following: HKey_Local_Machine on Local
Machine, System, CurrentControlSet, Services, Serial,
Parameters. Typically, no keys should be listed beneath
Parameters. Check the values of any keys listed to locate
the conflicting serial port(s).
- Delete any conflicting keys under Parameters. Highlight
the serial port key and press "Delete". Repeat
for each conflicting serial port configuration. Reboot
the system and check the event viewer to verify that the
error messages do not reoccur. The errors may reappear
later if any operations are attempted in Control Panel,
Ports.
- CAUTION: Any mistakes made in editing the registry may
have disasterous results requiring you to boot to a
different Control Set or to reload Windows NT.
- The following event viewer error message: "Source
ntx* could not be found. It contains the following
insertion string(s): ntx*" means?
- Go into Control Panel, Network.
- Highlight the Digi adapter and click on
"Remove".
- Choose "OK".
- Choose "Do Not Restart Now".
- Go into File Manager, choose the <WINNT
path>/System32 path. Delete the dgconfig.* file(s).
- Restart your system and reinstall the Digi driver.
- RAS Port Status
waivers between Hardware Failure, Line Non-Operational
and Normal, Waiting for Call.
This error can result from one of several different
causes:
- 1. Using 8 pin RJ45 cabling instead of 10 pin cabling. 10
pin RJ45 cabling is required for Remote Access Service.
2.
The modem.inf file which shipped with NT 3.51 is not
current or not correct. Check with the modem manufacturer
to obtain a more current version of the modem.inf file.
If you are using the unimodem with NT 4.0, be sure that
your modem type is supported by unimodem. Verify this
with your modem manufacturer. If the modem is not
supported by unimodem, refer to Microsoft Knowledge Base
document Q150808 on how to disable unimodem.
3. Not selecting the correct modem type in RAS.
4. With US Robotics Sportster modems, the dip switches
on the modem are not set correctly for use with RAS.
Switches 3, 7, and 8 should be down - different from
factory default.
5. The registry may have the wrong information. To see
if this is the case: Start the Registry editor by typing
"start regedt32" at a command prompt. From the
HKEY_LOCAL_MACHINE subtree, go to the following key:
\System\CurrentControlSet\Services\Asyncmac\Parameters\ports
This entry may be set to a value that is less than the
number of incoming ports available. If NetBEUI is not
loaded, this entry is not updated properly. If this is
the case, first install NetBEUI, then reinstall the Digi
driver, and then reinstall RAS. Simply editing the port
value in the registry is not suggested and will not
correct the problem (refer to Microsoft Knowledge Base
document Q138226).
6. The Digi hardware could be defective.
7. The system may be running out of resources. If this
is the case, disable some or all of the ports for
outgoing calls and make them incoming lines only. For
each outgoing connection/protocol pair, a Control Block
is required. This uses an amount of memory equal to:
(Number of ports)*(Protocols per port)*sizeof(Control
Block) However, DialIn ports have just one Control Block
for 256 connections.
- Remote Access Service is not
yielding expected throughput.
- For Windows NT 3.51:
- Edit the modem.inf and serial.ini files to indicate the
desired baud rate by following these steps:
- In the modem.inf file, which can be found in the
following subdirectory:
<NTpath>/system32/RAS/modem.inf in the
section corresponding to your modem type, the
specified parameters can be changed to match your
desired baud rate:
- Example:
- US Robotics Sportster 28800 VFC] <-your modem
type
- CALLBACKTIME=10
- DEFAULTOFF=compression
- MAXCARRIERBPS=115200 <- choose baud rate
- MAXCONNECTBPS=115200 <- choose baud rate
- <speaker_on>=M1
- <speaker_off>=M0
- <hwflowcontrol_on>=&H1&R2
- <hwflowcontrol_off>=&H0&R1
- <compression_on>=&K1
- <compression_off>=&K0
- .
- .
- .
- Also, in the serial.ini file, which can be found
in the following subdirectory:
<NTpath>/system32/RAS/serial.ini within
each section corresponding to each port on the
Digi board, the specified parameters can be
changed to match your desired baud rate.
- Example:
- [COM2]
- DEVICETYPE=Modem
- DEVICENAME=US Robotics Sportster 28800 VFC
- MAXCONNECTBPS=115200 <- choose baud rate
- MAXCARRIERBPS=115200 <- choose baud rate
- USAGE=ClientAndServer
- DEFAULTOFF=compression
- CLIENT_DEFAULTOFF=Compression
- INITIALBPS=115200 <- choose baud rate
- .
- .
- .
- For Windows NT 4.0:
- If you are using the unimodem with NT 4.0, go into
Control Panel, Modems, highlight the modem and click on
Properties. Change the Maximum Speed to the desired baud
rate.
- What type of
modem pooling software is available for NT?
Modem Pooling Applications are listed below:
- 1. SAPS
Supported by SpartaCom
Supports modem pooling on Windows, Windows NT, and
OS/2 Servers
- SpartaCom USA
- 1951 Airport Road
- Atlanta, GA 30341
- 770-946-9149
- FAX 770-946-5194
- Compuserve 70613,457
- SpartaCom Sales Europe B.V.
- Parelgris 48 STE 211 2718 NV Zoetermeer
- The Netherlands
- 31 79 614 140
- FAX 31 79 619 990
- Compuserve 100265,1625
- Email Spartacom@IB.COM
The SAPS Windows 95 client and server software is
downloadable from www.tspco.com.
2. WINport/FAXport
- Supported by LANSource
- Supports modem & faxmodem pooling on
WindowsNT, Novell, and OS/2 servers.
- LANSource
- 221 Dufferin Street STE 310A
- Toronto, Canada M6K 3J2
- 800-677-2727, 416-535-3555
- FAX 416-535-6225
Email sales@lansource.com
- What are the installation instructions for the PC/X
and MC/X under Windows NT?
The installation instructions are found in the pcx_nt.txt
document. This document may be downloaded from the BBS or
the ftp site.
- What options are available for testing
the ports under Windows NT?
- For COM1 through COM9, use the Terminal program located
in the Accessories folder. Choose Settings,
Communications, and select the port you have connected
the modem to. Configure the communications settings to
match the modem and choose "OK". A blinking
cursor will appear. Type "AT" and hit return.
The letters "AT" should be echoed back to the
console as well as an "OK". This will show that
data was sent to the modem and a response was received
back from the modem. If you have a Digi loopback
connector on the port, the characters that you type
within the terminal session should be echoed back to the
console. This will show that data is being both
transmitted and received on the port.
For COM1 through
COM256, use Digi's TTY program. This program is available
either on the BBS or the ftp site. Choose Settings, and
select the port you have connected the modem to.
Configure the communications settings to match the modem
and choose "OK". Then choose Action, Connect. A
blinking cursor will appear. Type "AT" and hit
return. The letters "AT" should be echoed back
to the console as well as an "OK". This will
show that data was sent to the modem and a response was
received back from the modem. If you have a Digi loopback
connector on the port, the characters that you type
within the terminal session should be echoed back to the
console. This will show that data is being both
transmitted and received on the port.
NOTE: It is possible to start two instances of
TERMINAL or TTY and test the ports by connecting them
with a standard "NULL MODEM" cable. Set each to
the same baud rate, parity, and stop bits. Try typing
some characters in the active window. If you see
characters appearing in the opposite window, then the
ports are communicating.
- I'm writing my own application and I am
not able to access any ports above COM9.
- In Windows NT, the ports above COM9 must be addressed
with the following naming convention: \\.\COM#. For
example, COM10 should be addressed as \\.\COM10. You may
also address COM1-9 with the same naming convention.
Windows NT will recognize either name.
- How do you install
printers on the Digi ports?
- Verify that you are using a null modem cable between the
Digi port and the printer. To set up the Digi ports for
printing, go into Print Manager. If you have not already
created a printer, select "Create Printer".
Fill in the required information for the new printer
(printer name, driver).
1. For the "Print to
:" option, select "Other", then select
"Local port".
2. Type in the Digi port name followed by a colon (for
example, COM5:). This will bring up the Ports applet.
3. Select the port you have just configured from the
list displayed, and choose "Settings". Set the
baud rate to 9600, data bits to 8, parity to none and
stop bits to 1.
4. Select "OK" and then "Close".
Repeat these steps for any additional printers you
need to add. For printers that have already been created,
select "Properties" for that printer, and then
follow the above instructions. Once you have configured
all the ports you will be using for printing, you must
restart NT. You may notice that the ports you have
configured do not show up under the "Print to:"
list. These will not display until after you restart NT.
Once you have restarted NT, go back to Print Manager,
and select "Properties" for each printer. Go to
the "Print to:" option, and select the Digi
port from the list displayed.
- The Modem
Xem is not being auto detected by RAS (Windows NT 3.5x).
- When the Modem Xem driver is installed, the modem.inf
entry for this modem type should be written to the
existing modem.inf file. However, if RAS is not already
installed when the Modem Xem is installed, there is no
existing modem.inf file to write to. In this case, once
RAS is installed, before adding the Modem Xem ports to
RAS, you must first go back into Control Panel, Network,
and configure the Modem Xem driver. Once you have viewed
the configuration, click on "OK" to exit the
Network settings applet. During the rebinding process,
the modem.inf entry for the Modem Xem product will be
written to the modem.inf file in the /system32/ras
directory. Once that is complete, restart NT, and
reconfigure RAS. The Modem Xem should now display as a
modem option and the modems should now be autodetected by
RAS.
Last updated January 3, 1997
93006061 Revision D.
|
|